Go top
Paper information

A novel rotor ground-fault-detection technique for synchronous machines with static excitation

C.A. Platero, F. Blázquez, P. Frías, M. Redondo

IEEE Transactions on Energy Conversion Vol. 25, nº. 4, pp. 965 - 973

Summary:

This paper presents a novel ground-fault-detection technique for synchronous machines. This technique is suitable for synchronous machines with static excitation systems, whose excitation field winding is fed by rectifiers through an excitation transformer. The main contribution of this new technique is that it can detect and discriminate both ac- and dc-side ground faults in the excitation system, without the need for traditional power injection sources. This detection technique is based on the frequency analysis of the voltages or currents at a grounding impedance placed at the excitation transformer neutral terminal. This technique has been validated through computer simulations and experimental laboratory tests.


Keywords: AC generator excitation, power generation protection, power system protection, synchronous generator excitation


JCR Impact Factor and WoS quartile: 2,489 (2010); 5,000 - Q1 (2023)

DOI reference: DOI icon https://doi.org/10.1109/TEC.2010.2040739

Published on paper: December 2010.

Published on-line: June 2010.



Citation:
C.A. Platero, F. Blázquez, P. Frías, M. Redondo, A novel rotor ground-fault-detection technique for synchronous machines with static excitation. IEEE Transactions on Energy Conversion. Vol. 25, nº. 4, pp. 965 - 973, December 2010. [Online: June 2010]


    Research topics:
  • *Smart Grids

pdf Preview
Request Request the document to be emailed to you.